MIRB rubber-plastic flexible integrated air duct

Product Introduction

Winduct® MIRB rubber-plastic flexible integrated air duct is made of fireproof grade B1 one-piece molded wear-resistant heat-insulating rubber-plastic material with embossing process + fireproof grade A2 fiber material. The air duct insulation thickness is 25mm, which is wear-resistant and has low air leakage.

Fire rating

Product Performance

Application

Suitable for low spaces in industrial, public and commercial areas

25mm

Core Advantages

Fire rating

B1

Easy installation, high cost performance

Insulation thickness

Application Scenario

Low space

B1 grade embossed wear-resistant rubber and plastic

Winduct® MIRB rubber-plastic flexible integrated air duct is made of fireproof grade B1 one-piece molded wear-resistant heat-insulating rubber-plastic material with embossing process + fireproof grade A2 fiber material. The air duct insulation thickness is 25mm, which is wear-resistant and has low air leakage.

Suitable for clean areas

IGA series full A-grade flexible integrated air duct

B1 intermediate insulation layer

IR series thermal insulation flexible integrated duct

A2 grade internal fireproof layer

D series fabric duct

MIRB series rubber and plastic flexible integrated air duct

H series flexible return air duct

Technical Parameters

Performance Project
Technical Parameters
Implementation Standards
Fire rating - outer layer
B1 non-combustible material
GB 8624-2012
Fire protection level - intermediate protection layer

B1 flame retardant material

GB/T 20284-2006
Thermal conductivity [W/(m·K)]
When the average temperature is 0℃, ≤0.036, the actual value is 0.031
GB/T 17794-2021
Wet resistance factor μ
≥1.5*10³, measured 1.5*10∧4
GB/T 17794-2021
Thermal resistance K[(m².k)/w]


Minimum thermal resistance of general air conditioning duct (lowest temperature of cold medium 15°C, highest temperature of hot medium 30"C) ≥0.81
GB/T 3923.1-2013


Anti-aging performance, 150h
Slightly wrinkled, no cracks, no deformation
GB/T 17794-2021
Antibacterial rate


Antibacterial rate ≥99%, with strong antibacterial effect; Antibacterial rate ≥90%, with antibacterial effect;
JC/T 939-2004


Air leakage per unit area


When the positive pressure is 1000pa, the maximum air leakage per unit area is ≤1.57 [m³/(h*㎡)], and the actual measurement is 0.93
JG/T 258-2018


Anti-condensation performance



After 2 hours of anti-condensation test on the air duct, there should be no condensation on the pipe wall and zipper joints (low temperature air supply 7~9℃, ambient temperature outside the air duct 32℃, relative humidity 80%, air duct wind speed 8m/s)
JG/T 258-2018



Duct strength

When the pressure is 3000 Pa, the appearance is normal with no damage or cracks.

JG/T 258-2018
Harmful gas release (mg/m³)



Formaldehyde ≤ 0.03, measured 0.012; Ammonia ≤ 0.06, measured 0.013; Benzene ≤ 0.03, measured 0; Toluene ≤ 0.06, measured 0.012; TVOC ≤ 0.2, measured 0.048

JG/T 258-2018



Fire rating - inner layer

A2 non-combustible material

GB 8624-2012